KOOL-TEMP ™ MARINE REFRIGERATION/FREEZER UNITS INSTALLATION INSTRUCTIONS AND OWNER’S MANUAL PRODUCED BY: MERMAID MANUFACTURING OF S.W., FL, IN
together, they allow the refrigerant to flow through the system without leaking out to the atmosphere. If needed, they can be undone to enable a faul
B: Wire Size: Consult ABYC tables for 3% volt drop. Never use less than 10 gauge wire. C: Overload Protection: Use either a breaker or fast-blow fus
(3) Run all applicable tests before assuming Module or Compressor to be faulty. B: Compressor Not Running, No Start Attempt. Probable cause Ac
connected retaining screw & then ensure that the 3-pin plug is seated firmly on the pins of the compressor. 9 Faulty compressor Remove the Modu
3 Thermostat type If you are planning to convert your ice box into a freezer, or as a spillover system, a freezer thermostat (0021) must be used. 4
E: System Runs, Box Temperature Too Low: 1 Thermostat setting Rotate thermostat knob to a lower number. 2 Thermostat type Check that you are us
F: Excessive Frost Build-Up: Note: This is the result of moist air being allowed to enter the box. Problems are compounded when cold air leaks from t
DANFOSS COMPRESSORS 12/24V AND 12/24V W/ 110V
WIRING OF DANFOSS ELECTRONIC MODULE 12/24V 12/24V + 110V FOLLOW THE WIRING DIAGRAM ABOVE AND DESCRIPTION BELOW TO MATC
TABLE OF CONTENTS SECTION 1 (OVERVIEW) A. Introduction to Mermaid SECTION 2 (INSTALLATION) A. Mounting Position B. Installation SECTION 3 (CONTROL
SECTION 8 (ELECTRICAL) A. Power Supply B. Wire Size C. Overload Protection D. Connections, Power E. Connections, Thermostat F. Connections, Fan SECT
Mermaid’s 12/24VDC model or our 12/24VDC & 110V with Auto Change-Over model, we are sure you will be pleased with their performance. Mermaid prov
SECTION 3 (CONTROL MODULE) A: Electronic Control Module: The Electronic Control Module is an integral part of the Danfoss BD35/50F compressor system
C: Compressor Non-Start: If the compressor does not start, the Module will stop the starting process, & attempt a re-start every 60 seconds. D:
NOTE TWO The Electronic Module, although designed for harsh & marine applications, can be damaged from either direct or incidental contact with wa
C: Thermostat Sensing Tube: Check to see where you need to attach the thermostat sensing tube before mounting the evaporator. The capillary tube (sil
contact with any electrical component either inside or outside the ice-box. If the sensing tube needs to be bent within the confines of the refrigerat